Leave Your Message
SPMK516T Desktop Process Calibrator (HART+Temperature)

SPMK516T Desktop Process Calibrator (HART+Temperature)

Measurement and simulation function    
Measures 13 types of thermocouples and 11 types of RTDs
Connect with SPMKSDP external pressure module 
3.5-inch high-resolution TFT display
DC24V power supply isolated from measurement and output

    SPMK212C pressure source is a high precision pneumatic handheld pressure generator. It provides stable micro pressure from -0.5 to 0.5bar (-7-7psi). The simple structure and easy operation make it a perfect equipment for calibrating differential pressure gauges, pressure transmitters, pressure sensors, and other low pressure (vacuum) instruments.

    SPMK516T Multifunction Calibrator

    51XT

    Product Characteristics

    •  Variety of functions 
      Calibrate pressure, temperature, voltage, current, frequency, pulse, resistance. Both measurement and output functions.
    • Measurement and output functions
      Measures 13 types of thermocouples and 11 types of RTDs and provides analog output with cold end compensation.
    • Data storage function
      No need to worry about data loss. Supports output methods such as step or program.
    • Built-in HART hand manipulator function
      Calibration and maintenance of HART-type instruments can be performed, including management of basic instrument information, range migration, and zero and full scale calibration. (518T only)
    • Supporting external pressure modules
      Spake Model SDP Modular Intelligent Digital Pressure Calibrator. (only for 517T and 518T ) (optional)
    •  Task management function
    • Analog Transmitters
      Generate precise electrical, temperature or pressure signals.
    • Provides a wide range of commonly used tools
      Thermal engineering treasure trove, user-built RTD library, temperature and pressure unit conversion.
    • Automatic cold-end compensation technology
      Built-in cold end insulation module for fast tracking of temperature changes.
    • 5.6" high resolution TFT display
    • Free choice of Chinese and English languages
    • RS232 interface and open communication protocol
    • Provides a 24VDC loop power supply with measurement and output isolated from each other
    • Support online firmware upgrade
    • Warranty: 1 year

    Product Functions

    Function SPMK516T SPMK517T SPMK518T
    Measurement Millivolts
    Voltage
    Current
    Frequency
    Pulse
    Resistance
    On-off
    11 RTDs
    13 thermocouples
    Output Millivolt current
    Voltage
    Current
    Frequency
    Resistance
    Simulate 11 RTDs
    Simulate 13 thermocouples
    Other functions HART communication  
    External pressure module  
    Thermal book
    Step programming output
    24V loop current
    Simulating transmitter
    RS232 communication
    Storage

    Note:  "★" indicates available; 
     ① External pressure module means SDP Modular Intelligent Digital Pressure Calibrator produced by our company.

    Technical Parameters

    Electrical Signal Measurement Specifications (Ambient Temperature(20±5)°C, 1 yearAccuracy)

    Signal

    Range

    Accuracy

    Resolution

    Current

    (-3030)mA

    ±(0.01%RD+0.005%FS)

    0.1μA

    Voltage

    (-3030)V

    ±(0.01%RD+0.005%FS)

    0.1mV

    Millivolts

    (-7575)mV

    ±(0.01%RD+0.005%FS)

    0.1μV

     

    Resistance

    R-3W

    (0400)Ω

    (04000)Ω

    ±(0.02%RD+0.005%FS)

    1mΩ

    10mΩ

    R-4W

    (0400)Ω

    (04000)Ω

    ±(0.01%RD+0.005%FS)

    1mΩ

    10mΩ

    Frequency

    (150000)Hz

    ±(0.005%RD+0.002%FS)

    1Hz

    Pulse

    0999999

    ±1 pulse

    1

    Switch (on/off)

    If the switch is equipped with an inspection voltage, the voltage range is (3~24)V

    Thermocouples

    KEJTNRSBCDGLU

    RTDs

    Pt1000(385)Pt500(385)Pt100(385)Pt100(3916)Pt100(3926)Pt10(385)Cu10(427)Cu50(428)Cu100(428)Ni120(672)Ni100(618)

    Stress

    Refer to the Pressure Range Selection Chart (only for SPMK517T, SPMK518T).

    Electrical Output Specifications (Ambient Temperature (20±5)℃,1 year accuracy)

    Signal Range Accuracy Resolution
    Current (022)mA ±(0.02%RD+0.005%FS) 0.1μA
    Voltage (012)V ±(0.02%RD+0.005%FS) 0.1mV
    Millivolts (-10100)mV ±(0.02%RD+0.005%FS) 1μV
    Resistance (0400)Ω ±(0.02%RD+0.005%FS) 1mΩ
    (4004000)Ω ±(0.03%RD+0.01%FS) 10mΩ
    Frequency (050000)Hz ±(0.005%RD+0.002%FS) 0.1Hz
    Pulse 0999999 ±1 pulse 1
    24VDC (24±0.5)V Maximum belt load 50mA
    Simulating Thermocouple KEJTNRSBCDGLU
    Simulating RTDs Pt1000(385)Pt500(385)Pt100(385)Pt100(3916)Pt100(3926) Pt10(385)Cu10(427)Cu50(428)Cu100(428)Ni120(672)Ni100(618)

    Measurement using thermocouples and analog thermocouple output temperature specifications (Ambient temperature (20±5)℃)

    Thermocouple type Reference Temperature range () Tolerance temperature range () Maximum permissible error ()
    Measurement Output
    Type K IEC584 -270~1372 -200~-100 ±0.4 ±0.6
    -100~600 ±0.3 ±0.3
    600~1372 ±0.4 ±0.5
    Type E IEC584 -270~1000 -200~-100 ±0.3 ±0.4
    -100~600 ±0.2 ±0.2
    600~1000 ±0.2 ±0.4
    Type J IEC584 -210~1200 -210~-100 ±0.3 ±0.4
    -100~1200 ±0.3 ±0.3
    T-shaped IEC584 -270~400 -200~0 ±0.4 ±0.5
    0~300 ±0.2 ±0.3
    300~400 ±0.2 ±0.2
    Type N IEC584 -270~1300 -200~-100 ±0.5 ±0.6
    -100~1300 ±0.4 ±0.5
    Type R IEC584 -50~1768 -50~100 ±1.4 ±1.5
    100~500 ±0.6 ±0.7
    500~1768 ±0.7 ±0.7
    S-shaped IEC584 -50~1768 -50~100 ±1.1 ±1.2
    100~400 ±1.0 ±1.1
    400~1768 ±0.7 ±0.8
    Type B IEC584 0~1820 0~450 ±3.8 ±3.8
    450~800 ±0.9 ±1.0
    800~1200 ±0.6 ±0.7
    1200~1820 ±0.6 ±0.8
    Type C ASTM E988 0~2315 0~1000 ±0.6 ±0.7
    1000~1800 ±0.8 ±1.0
    1800~2315 ±1.2 ±1.5
    Type D ASTM E988 0~2315 0~100 ±0.6 ±0.6
    100~1100 ±0.5 ±0.6
    1100~2000 ±0.8 ±1.0
    2000~2315 ±1.0 ±1.4
    Type G ASTM E1751 0~2315 0~200 ±2.4 ±2.5
    200~400      ±0.5 ±0.6
    400~1400     ±0.4 ±0.6
    1400~2315     ±0.8 ±1.0
    Type L DIN43710 -200~900 -200~-100 ±0.3 ±0.5
    -100~400    ±0.2 ±0.3
    400~900    ±0.5 ±0.6
    Type U DIN43710 -200~600 -200~0 ±0.5 ±0.4
    0~600 ±0.3 ±0.5

    Note: Thermocouple type C is WRe5-WRe26, Thermocouple type D is WRe3-WRe25. 

    Measured and analog RTD output temperature specifications using RTD (Ambient temperature (20±5)°C)

    RTD type Reference Temperature range (°C) Tolerance temperature range () Maximum permissible error ()
    Measurement Output
    3-wire 4-wire
    Pt1000385 IEC751 -200~850 -100~200 ±0.13 ±0.08 ±0.29
    200~600 ±0.24 ±0.13 ±0.45
    600~840 ±0.32 ±0.19 ±0.56
    Pt500385 IEC751 -200~850 -100~200 ±0.22 ±0.16 ±0.35
    200~600 ±0.35 ±0.22 ±0.56
    600~850 ±0.39 ±0.28 ±0.69
    Pt100385 IEC751 -200~850 -100~200 ±0.18 ±0.14 ±0.15
    200~600 ±0.27 ±0.18 ±0.21
    600~850 ±0.36 ±0.29 ±0.35
    Pt1003926 Minco -200~850 -100~200 ±0.18 ±0.14 ±0.15
    Application 200~600 ±0.27 ±0.18 ±0.21
    Aid #18 600~850 ±0.36 ±0.29 ±0.35
    Pt1003916 JIS1604 -200~850 -100~200 ±0.18 ±0.14 ±0.15
    200~600 ±0.27 ±0.18 ±0.21
    600~850 ±0.35 ±0.29 ±0.35
    Pt10385 IEC751 -200~850 -100~200 ±0.68 ±0.64 ±0.66
    200~600 ±0.85 ±0.82 ±0.79
    600~850 ±0.98 ±0.89 ±1.09
    Cu100428 JB/T8623—1997 -50~150 -50~150 ±0.15 ±0.10 ±0.18
    Cu50428 JB/T8623—1997 -50~150 -50~150 ±0.19 ±0.17 ±0.20
    Cu10427 Minco -100~260 -100~260 ±0.65 ±0.58 ±0.62
    Application
    Aid #18
    Ni120672 Edison curve #7 -70~270 -70~270 ±0.08 ±0.06 ±0.08
    Ni100618 DIN43760 -70~190 -70~190 ±0.10 ±0.07 ±0.10

     

    General Technical Indicators

    Display 6-digit display
    Usage environment Ambient temperature: (-10~50)℃; Relative humidity: <90% non-condensing; Atmospheric pressure: (86~106)kPa.a
    Storage environment Ambient temperature: (-20~60)℃; Relative humidity: <90% non-condensing
    Power supply mode 220VAC 50Hz
    Overall dimensions 415mm(L) x 375mm(W) x 240mm(H)
    Weight 7.6kg
    Warranty 1 year

    Ordering Information

    SPMK510/ SPMK516/SPMK517/SPMK518 multifunction calibrators.

    Accessories(included)

    Serial number Description QTY Picture
    1 Mainframe 1 pc 1732086264464
    2 Power cord 1 pc 1732086276479
    3 1 red meter pen cable, 1 black meter pen cable, 1 red alligator clip, 3 set 1731912715830(1)
    1 black alligator clip
    4 Seven-core signal cable (SPMK517T, SPMK518T only) 1 pc 1731912730502(1)
    5 Dedicated short routes 1 pc 1732019607533
    6 Instructions for use 1 pc  
    7 Test reports 1 pc  

    Optional Accessories

    Serial number Description Serial number
    1 SDP Modular Intelligent Digital Pressure Calibrator 1731920634362  
    (Only for SPMK517T, SPMK518T )
    2 SDP Pressure Module Connection Cable (only with SDP Pressure Module)  1731912775250(1)
    3 RS232 communication cable 1731912793929  

    123

    1732016915483

    Packing option 1, without carrying case.

    Packing Dimension: 38x32x26cm
    G.W: 3.0 kg approximately

    1732016927507

    Packing option 2, with Aluminum carrying case.

    Packing Dimension: 49X43X29cm
    G.W: 6.0 kg approximately
    (Aluminum carrying case cost extra)